Blog | Sensonics

Cooling Tower Fan Vibration Monitoring: Building a Hardwired Trip System That Keeps Running

Written by John King | Nov 26, 2026, 2:18:37 PM

Cooling tower fans rarely make headlines, but when one fails the cost is newsworthy: lost cooling capacity, damaged gearboxes and blades, and in the worst case a fan assembly that comes apart at height. A dependable cooling tower fan vibration monitoring system is what stands between an early warning and an unplanned outage.

Sensonics recently designed, built and delivered a complete hardwired trip system for the cooling tower fans at a major petrochemical plant. This article walks through how it was put together and why each design choice matters for anyone specifying fan protection.

Project at a glance

 

Industry

Petrochemicals

Application

Cooling tower fan vibration monitoring and protection

Trip method

Hardwired relay trips to an external relay panel

Sensonics scope

Monitoring cubicle with 20 × DN26 G3 monitors, wiring, drawings and handbook

Outside scope

External relay panel

Why cooling tower fans need dedicated protection

Large induced-draught cooling tower fans run continuously in a hostile environment: wet, warm air, wide temperature swings and long drive shafts between motor, gearbox and fan. Faults tend to develop gradually and then accelerate. Common causes include:

  • Blade imbalance from icing, debris build-up, fouling, erosion or a change in blade pitch
  • Gearbox bearing and gear wear
  • Drive shaft misalignment or coupling damage
  • Loosened mountings or structural degradation of the fan deck

Each of these shows up first as a rise in vibration. Catching that rise early, and tripping the fan before damage spreads, is the job of the protection system.

For this project the customer specified hardwired trips. Rather than routing the shutdown decision through a DCS or PLC network, each monitor drives a relay contact directly into the trip circuit. That keeps the protective path simple, independent of plant networks and easy to prove during commissioning and routine testing.

The solution: one cubicle, twenty DN26 G3 monitors

The system is built around the Sensonics floor-standing equipment cubicle, housing 20 DN26 G3 machine protection monitors. Everything arrives pre-wired, tested and documented, so site work is limited to landing field cables and connecting to the customer's relay panel.

Feature

Detail

Enclosure

Rittal VX frame, 2000 mm tall (incl. 100 mm plinth), 800 mm wide, 400 mm deep

Monitors

20 × DN26 G3, 24 V DC, on a front-facing panel for easy viewing

Outputs per channel

Alarm relay to the external trip panel, plus a 4–20 mA signal for the control system

Cable entry

All incoming and outgoing cables through a gland plate in the roof

Access

Single lockable front door; double rear doors with IP55 filtered vents

The DN26 G3 is a compact, DIN-rail mounted protection monitor. It accepts IEPE accelerometers, velocity transducers and API 670 proximity probes, and offers two vibration channels plus a speed/phase channel. Each module has its own display, configurable alarm levels and relay outputs, so every measurement point has an independent protection channel. For this application each DN26 G3 measures velocity vibration, with a range of measurement algorithms available to suit the sensor type and the speed of the equipment being monitored.

The signal path for each fan measurement point is deliberately short:

Figure 1: Signal path for one fan measurement point

The trip decision is made in the monitor and passed as a dry relay contact; the 4–20 mA output is for indication only and plays no part in the trip.

Designed so protection keeps running

A protection system is only useful if it is available when the fault arrives. Several features of the design exist purely to keep the monitors powered and working.

Fully redundant power. Two independent mains supplies feed the cubicle through separate isolators, each fused at 20 A through BS88 fuses. Each feeds its own 100–240 V AC to 24 V DC power supply, and a diode module combines the two outputs. The system runs from either supply or both, so losing one feed does not interrupt protection.

Individual fusing. Every DN26 G3 has its own 24 V DC distribution fuse. A fault on one module cannot take down its neighbours, and any single unit can be isolated and swapped without disturbing the other 19 channels.

Segregated wiring. Signal and power wiring run in separate trunking on the rear panel. Keeping low-level sensor signals away from power cabling mitigates the risk of interference and false readings.

Practical access. Monitors sit on a forward-facing panel for operators, while power and signal distribution are on the rear panel. Double rear doors allow installation where floor space behind the cubicle is limited, and filtered IP55 vents top and bottom keep the electronics cool.

What operators see

Each DN26 G3 is pre-configured by Sensonics to show a bargraph and numeric value for its channel, with the warning and trip levels marked on the same screen. The bargraph changes colour with machine condition:

Colour

Meaning

Green

Healthy: between minimum and the warning alarm

Amber

Warning: between the warning and danger alarms

Red

Danger: above the danger alarm

An operator walking past the cubicle can see the state of every fan at a glance. Alarm settings can be adjusted from the front-panel keypad, or from a laptop connected to the front RJ45 port using the supplied software.

Each monitor also has a dedicated integrity relay that flags a module or sensor fault, so a broken cable is reported rather than silently masking a real problem. A hardwired reset input lets operators reset alarms once the cause has been dealt with.

Low maintenance by design

The monitors are factory set and need no calibration on installation. Routine care is limited to occasional checks for dust build-up, cleaned with a vacuum.

If a module does fail, the individual fusing means it can be isolated and replaced without shutting down the rest of the system. The unit is then returned to Sensonics for examination and repair. Every system ships with a full handbook covering the general assembly, power distribution, loop wiring, signal terminal and earth wiring drawings, so site teams have everything needed for fault-finding and future modifications.

What to look for when specifying fan protection

Whether you are protecting a single fan or a full bank of cells, the same principles apply:

  1. One independent channel per measurement point, so a fault on one channel never blinds another.
  2. A hardwired trip path that does not depend on plant networks or software.
  3. Redundant power with individual fusing, so protection survives a lost supply or a failed module.
  4. Clear local indication so operators see developing problems before they become trips.
  5. Sensor and cable integrity monitoring, so faults in the measurement chain are reported, not hidden.
  6. Complete documentation to support commissioning, testing and future changes.

Talk to Sensonics

Sensonics designs and builds complete vibration monitoring and protection systems, from single DN26 G3 modules to fully wired, tested cubicles ready for site. If you are planning new cooling tower fan protection or replacing an ageing system, contact our team at sales@sensonics.co.uk or +44 (0)1442 876 833 to discuss your application.