Cooling tower fans rarely make headlines, but when one fails the cost is newsworthy: lost cooling capacity, damaged gearboxes and blades, and in the worst case a fan assembly that comes apart at height. A dependable cooling tower fan vibration monitoring system is what stands between an early warning and an unplanned outage.
Sensonics recently designed, built and delivered a complete hardwired trip system for the cooling tower fans at a major petrochemical plant. This article walks through how it was put together and why each design choice matters for anyone specifying fan protection.
|
Project at a glance |
|
|
Industry |
Petrochemicals |
|
Application |
Cooling tower fan vibration monitoring and protection |
|
Trip method |
Hardwired relay trips to an external relay panel |
|
Sensonics scope |
Monitoring cubicle with 20 × DN26 G3 monitors, wiring, drawings and handbook |
|
Outside scope |
External relay panel |
Large induced-draught cooling tower fans run continuously in a hostile environment: wet, warm air, wide temperature swings and long drive shafts between motor, gearbox and fan. Faults tend to develop gradually and then accelerate. Common causes include:
Each of these shows up first as a rise in vibration. Catching that rise early, and tripping the fan before damage spreads, is the job of the protection system.
For this project the customer specified hardwired trips. Rather than routing the shutdown decision through a DCS or PLC network, each monitor drives a relay contact directly into the trip circuit. That keeps the protective path simple, independent of plant networks and easy to prove during commissioning and routine testing.
The system is built around the Sensonics floor-standing equipment cubicle, housing 20 DN26 G3 machine protection monitors. Everything arrives pre-wired, tested and documented, so site work is limited to landing field cables and connecting to the customer's relay panel.
|
Feature |
Detail |
|
Enclosure |
Rittal VX frame, 2000 mm tall (incl. 100 mm plinth), 800 mm wide, 400 mm deep |
|
Monitors |
20 × DN26 G3, 24 V DC, on a front-facing panel for easy viewing |
|
Outputs per channel |
Alarm relay to the external trip panel, plus a 4–20 mA signal for the control system |
|
Cable entry |
All incoming and outgoing cables through a gland plate in the roof |
|
Access |
Single lockable front door; double rear doors with IP55 filtered vents |
The DN26 G3 is a compact, DIN-rail mounted protection monitor. It accepts IEPE accelerometers, velocity transducers and API 670 proximity probes, and offers two vibration channels plus a speed/phase channel. Each module has its own display, configurable alarm levels and relay outputs, so every measurement point has an independent protection channel. For this application each DN26 G3 measures velocity vibration, with a range of measurement algorithms available to suit the sensor type and the speed of the equipment being monitored.
The signal path for each fan measurement point is deliberately short:
Figure 1: Signal path for one fan measurement point
The trip decision is made in the monitor and passed as a dry relay contact; the 4–20 mA output is for indication only and plays no part in the trip.
A protection system is only useful if it is available when the fault arrives. Several features of the design exist purely to keep the monitors powered and working.
Fully redundant power. Two independent mains supplies feed the cubicle through separate isolators, each fused at 20 A through BS88 fuses. Each feeds its own 100–240 V AC to 24 V DC power supply, and a diode module combines the two outputs. The system runs from either supply or both, so losing one feed does not interrupt protection.
Individual fusing. Every DN26 G3 has its own 24 V DC distribution fuse. A fault on one module cannot take down its neighbours, and any single unit can be isolated and swapped without disturbing the other 19 channels.
Segregated wiring. Signal and power wiring run in separate trunking on the rear panel. Keeping low-level sensor signals away from power cabling mitigates the risk of interference and false readings.
Practical access. Monitors sit on a forward-facing panel for operators, while power and signal distribution are on the rear panel. Double rear doors allow installation where floor space behind the cubicle is limited, and filtered IP55 vents top and bottom keep the electronics cool.
Each DN26 G3 is pre-configured by Sensonics to show a bargraph and numeric value for its channel, with the warning and trip levels marked on the same screen. The bargraph changes colour with machine condition:
|
Colour |
Meaning |
|
Green |
Healthy: between minimum and the warning alarm |
|
Amber |
Warning: between the warning and danger alarms |
|
Red |
Danger: above the danger alarm |
An operator walking past the cubicle can see the state of every fan at a glance. Alarm settings can be adjusted from the front-panel keypad, or from a laptop connected to the front RJ45 port using the supplied software.
Each monitor also has a dedicated integrity relay that flags a module or sensor fault, so a broken cable is reported rather than silently masking a real problem. A hardwired reset input lets operators reset alarms once the cause has been dealt with.
The monitors are factory set and need no calibration on installation. Routine care is limited to occasional checks for dust build-up, cleaned with a vacuum.
If a module does fail, the individual fusing means it can be isolated and replaced without shutting down the rest of the system. The unit is then returned to Sensonics for examination and repair. Every system ships with a full handbook covering the general assembly, power distribution, loop wiring, signal terminal and earth wiring drawings, so site teams have everything needed for fault-finding and future modifications.
Whether you are protecting a single fan or a full bank of cells, the same principles apply:
Sensonics designs and builds complete vibration monitoring and protection systems, from single DN26 G3 modules to fully wired, tested cubicles ready for site. If you are planning new cooling tower fan protection or replacing an ageing system, contact our team at sales@sensonics.co.uk or +44 (0)1442 876 833 to discuss your application.